Title: Distribution network reconfiguration validation with uncertain loads: network configuration determination and application
Authors: Bai, Xuefeng
Mavrocostanti, Yiango
Strickland, Dani
Harrap, Christopher
Issue Date: 2016
Publisher: © The Institution of Engineering and Technology
Citation: BAI, X. ... et al, 2016. Distribution network reconfiguration validation with uncertain loads: network configuration determination and application. IET Generation, Transmission and Distribution, 10 (12), pp. 2852-2860.
Abstract: Automatic load transfer (ALT) on the 11 kV network is the process by which circuit breakers on the network are switched to form open points in order to feed load from different primary substations. Some of the potential benefits that may be gained from dynamically using ALT include maximising utilisation of existing assets, voltage regulation and reduced losses. One of the key issues, that has yet to be properly addressed in published research, is how to validate that the modelled benefits really exist. On an 11 kV distribution network where the load is continually changing and the load on each distribution substation is unlikely to be monitored - reduction in losses from moving the normally open point is particularly difficult to prove. This study proposes a method to overcome this problem and uses measured primary feeder data from two parts of the Western Power Distribution 11 kV Network under different configurations. The process of choosing the different configurations is based on a heuristic modelling method of locating minimum voltages to help reduce losses.
Description: This article was published in the journal IET Generation, Transmission and Distribution [© Institution of Engineering and Technology] and the definitive version is available at: http://dx.doi.org/10.1049/iet-gtd.2015.0734. The affiliation information provided in the published version of this paper is incorrect. The correct affiliation information is given below: Xuefeng Bai1, Yiango Mavrocostanti2, Dani Strickland1, Chris Harrap2 1 School of Engineering and Applied Science, Aston University, Birmingham Triangle, Birmingham, UK 2 Western Power Distribution, Pegasus Business Park, East Midlands, UK. The correct affiliation information can also be found at doi: 10.1049/iet-gtd.2016.1702
Version: Accepted for publication
DOI: 10.1049/iet-gtd.2015.0734
URI: https://dspace.lboro.ac.uk/2134/24982
Publisher Link: http://dx.doi.org/10.1049/iet-gtd.2015.0734
ISSN: 1751-8687
Appears in Collections:Published Articles (Mechanical, Electrical and Manufacturing Engineering)

Files associated with this item:

File Description SizeFormat
Distribution_network_reconfiguration_validation_with_uncertain_loads.pdfAccepted version650.66 kBAdobe PDFView/Open

 

SFX Query

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.